§ 25.37. Same - Inlet requirements.  


Latest version.
  • No person shall install or allow to exist any inlet discharging water from a water supply to be used for domestic or human consumption or industrial purpose in or into any tank, cistern, reservoir or receptacle for storage or use of water on the consumer's premises unless such inlet discharges such water at a height at least double the diameter of the inlet pipe above the maximum possible high-water level of such tank, cistern, reservoir, or other receptacle for the storage or use of water, or unless such inlet is equipped with an approved backflow prevention device. (Ord. No. 793, § 3.10; Ord. No. 985, § Appx. A.)